Baumer AMG11 N29 Manual - Page 41

Browse online or download pdf Manual for Media Converter Baumer AMG11 N29. Baumer AMG11 N29 41 pages. Absolute encoders with profinet interface

Baumer AMG11 N29 Manual
7.3.3.

No position data

Encoder DUO-LED lit green continuous, LED of connected port is green continuous, but PLC does not
recognize any position data.
• The encoder's device name is clear (""), and PLC cannot automatically assign the proper name because
automatic assignment wasn't projected or no Topoplogy Planning was done.
• Make sure the I/O encoder addresses are within the cyclic updated process mapping. Size and position of
process mapping or encoder I/O address may require adjustment.
• No I/O module present in encoder HW configuration.
• No topology planning executed. Other port than projected has been connected (operating modes IRT).
7.3.4.

PLC error LED is lit

Encoder operational, but error LED at PLC is lit
• Operating mode RT: Topology planning executed. Other port than projected has been connected.
• Diagnostic alarm is present

Baumer_BUDE-PROFINET_MA_EN.docx

MB707.E – 16A3 – Firmware Version 2.10 and later
14.06.2016 / bja
41/41
P.O. Box 12 69 43 · D-10609 Berlin, Germany
Phone: +49 (0)30/69003-0 · Fax: +49 (0)30/69003-104
[email protected] · www.baumer.com
Baumer Hübner GmbH
Technical modification reserved