Baumer AMG11 N29 Handmatig - Pagina 41

Blader online of download pdf Handmatig voor {categorie_naam} Baumer AMG11 N29. Baumer AMG11 N29 41 pagina's. Absolute encoders with profinet interface

Baumer AMG11 N29 Handmatig
7.3.3.

No position data

Encoder DUO-LED lit green continuous, LED of connected port is green continuous, but PLC does not
recognize any position data.
• The encoder's device name is clear (""), and PLC cannot automatically assign the proper name because
automatic assignment wasn't projected or no Topoplogy Planning was done.
• Make sure the I/O encoder addresses are within the cyclic updated process mapping. Size and position of
process mapping or encoder I/O address may require adjustment.
• No I/O module present in encoder HW configuration.
• No topology planning executed. Other port than projected has been connected (operating modes IRT).
7.3.4.

PLC error LED is lit

Encoder operational, but error LED at PLC is lit
• Operating mode RT: Topology planning executed. Other port than projected has been connected.
• Diagnostic alarm is present

Baumer_BUDE-PROFINET_MA_EN.docx

MB707.E – 16A3 – Firmware Version 2.10 and later
14.06.2016 / bja
41/41
P.O. Box 12 69 43 · D-10609 Berlin, Germany
Phone: +49 (0)30/69003-0 · Fax: +49 (0)30/69003-104
[email protected] · www.baumer.com
Baumer Hübner GmbH
Technical modification reserved