Cardax FT Controller 3000 Installation Note - Page 10
Browse online or download pdf Installation Note for Controller Cardax FT Controller 3000. Cardax FT Controller 3000 11 pages.
Technical specification
Power required:
Environmental:
Maximum number of ...
Fuses
EMI Cable Shields
Note: The Cardax FT Controller 3000 has no replaceable parts.
NOTE:
This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
•
•
•
Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by Cardax (International) Ltd could void the
user's authority to operate this equipment.
:
:
002132943
002132943
:
:
:
002132943
002132943
002132943
1 0
Voltage
Current
Operating temperature
Humidity
Inputs
Outputs
RS485 ports
Ethernet ports
RS232 ports
FS1 power in
FSA1 to FSA4 power out
Impedance at 25MHz must be greater than 60 Ohms
Impedance at 100MHz must be greater than 100 Ohms
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
13.6 V DC ± 15%
290mA
(Without relays operated)
610mA
(All relays operated)
The above currents exclude external devices such as
readers and alarm sounders.
0
0
-10
C to +55
C
95% non-condensing
16
(4 state monitored)
8
(relay contact current rating at 24 V DC/AC
5 A resistive)
1
(currently not supported)
1
1
(plus 1 dedicated diagnostic port)
1.5 A Resettable fuse
500mA Resettable fuse (power out for readers and
(processor)
monitoring devices)
Part number 3E1089 R3