Cardax FT Controller 3000 Installation Note - Page 8
Browse online or download pdf Installation Note for Controller Cardax FT Controller 3000. Cardax FT Controller 3000 11 pages.
Run LED
The red, Run, LED (D1) flashes to indicate the operating status of the Cardax FT Controller
as detailed in the following table:
Flash
Fast
1 flash
2 flashes
3 flashes
4 flashes
5 flashes
6 flashes
Short flash
long flash
(1s cycle)
* Should an SSL key data file be lost or corrupted, requests for replacements should be
made to your local Cardax office. You will need to supply the last six digits of the Cardax
FT Controller MAC address.
8
Sequence timing
130ms on, 130ms off
(4 Hz flash)
500 ms on, 500ms off
(1 Hz flash)
2 flashes - pause
(each flash is 50ms on, 400ms
off and the pause is 1.2s)
3 flashes - pause
(each flash is 50ms on, 400ms
off and the pause is 1.2s)
4 flashes - pause
(each flash is 50ms on, 400ms
off and the pause is 1.2s)
5 flashes - pause
(each flash is 50ms on, 400ms
off and the pause is 1.2s)
6 flashes - pause
(each flash is 50ms on, 400ms
off and the pause is 1.2s)
450ms on, 50ms off
(2 Hz flash)
100ms on, 250ms off (short),
400ms off, 250ms on (long)
Meaning
Initialising
Normal running
Cardax FT Controller has an IP but no
configuration, or has been configured
incorrectly
Cardax FT Controller requires an IP
address - Ensure BootP Service
(CCFTBPS.exe) is running, the Cardax
FT Controller is configured correctly,
and it has connected to the network.
No private key or certificate loaded
(* see note below for obtaining keys
and certificates)
Invalid private key or certificate loaded,
or key and certificate do not match the
Cardax FT Controller serial number
The Cardax FT Controller has dropped
its code. Load code again via serial
COM port.
Cardax FT Controller resetting
Boot code monitor running
Part number 3E1089 R3