Also for Bosch FAP-OC 500Series: Installation Instructions Manual (21 pages), Instructions For Use Manual (40 pages), Installation Manual (6 pages), Installation Manual (28 pages), User Manual (48 pages), User Manual (48 pages), Installation Manual (28 pages), Use And Care Manual (44 pages), Installation Manual (32 pages), Use And Care Manual / Installation Instructions (40 pages), Quick Reference Manual (4 pages), Use And Care Manual (27 pages), Installation Manual (24 pages), Installation Manual (32 pages), Use And Care Manual (24 pages), Installation Manual (28 pages), Service Manual (41 pages), Use And Care Manual (21 pages), Installation Manual (32 pages), Service Manual (36 pages), Installation Manual (32 pages), Quick Start And Safety Manual (13 pages)

Bosch FAP-OC 500Series Product Information
Product Information 500 Series LSN Fire Detectors (EU)

4. Technical Specifications

4.1. Detector and Trim Ring

Detector type
Detection principle
Special features
Operating voltage
Current consumption
Individual display
Alarm output
Indicator output
Response sensitivity
− O unit
− Gas unit
Max. monitoring area
Maximum installation height
Minimum installation height
Minimum distance to lamps
Permitted air speed
Perm. operating temperature
Permitted relative humidity
Protection category accord-
ing to EN 60 529
Interference immunity
Dimensions
− Detector without trim ring
− Detector with trim ring
Housing material
Color of detector housing
Color of det. front panel
− White variant
− Transparent variant (−P)
Weight (without / with pack.)
− Detector
− Trim ring FAA−500−TR(−P)
VdS Approval number
EC Certification of Conform.
FAP−OC 500/FAP−OC 500−P
Combination of scattered light
and combustion gas measure-
ment
Contamination detection
Drift compensation in optical
and in gas measuring unit
20 V DC to 33 V DC
Two−color LED: red / green
By data word via two−wire signal line
Open collector, switches 0 V over 1.5 kΩ, max. 15 mA
< 0,36 dB/m (EN 54−7)
In ppm range
120 m
16 m (Heed local guidelines)
−10 °C to +50 °C
< 95 % (non−condensing)
IP 33
According to VdS 2110, DIN EN 50130−4 and UL 268
∅ 113 x 55 mm (without base) / ∅ 113 x 70 mm (with base)
∅ 150 x 55 mm (without base) / ∅ 150 x 70 mm (with base)
Signal white, RAL 9003
Transparent / silver gray, RAL 7001
Approx. 180 g / 370 g
G 204 130
0786−CPD−20184
Page 14
FAP−O 500/FAP−O 500−P
Scattered light measurement
Contamination detection
Drift compensation in optical
unit
3.5 mA
< 0,18 dB/m (EN 54−7)
2
(Heed local guidelines)
Out of arm's reach
0.5 m
20 m/s
−20 °C to +65 °C
Polycarbonate
Signal white, matt
Approx. 170 g / 360 g
Approx. 30 g / 60 g
G 204 129
0786−CPD−20183
BDL−F.01U.025.876
ST−FIR/PRM1 / zab
PI − 34.70 en
IP 53
A5.en/ 02.02.2006