Bosch FAP-OC 500Series Product Information - Page 12

Browse online or download pdf Product Information for Washer Bosch FAP-OC 500Series. Bosch FAP-OC 500Series 40 pages. Built-in wall ovens
Also for Bosch FAP-OC 500Series: Installation Instructions Manual (21 pages), Instructions For Use Manual (40 pages), Installation Manual (6 pages), Installation Manual (28 pages), User Manual (48 pages), User Manual (48 pages), Installation Manual (28 pages), Use And Care Manual (44 pages), Installation Manual (32 pages), Use And Care Manual / Installation Instructions (40 pages), Quick Reference Manual (4 pages), Use And Care Manual (27 pages), Installation Manual (24 pages), Installation Manual (32 pages), Use And Care Manual (24 pages), Installation Manual (28 pages), Service Manual (41 pages), Use And Care Manual (21 pages), Installation Manual (32 pages), Service Manual (36 pages), Installation Manual (32 pages), Quick Start And Safety Manual (13 pages)

Bosch FAP-OC 500Series Product Information
Product Information 500 Series LSN Fire Detectors (EU)

3. Programming

LSN detectors are programmed according to the required operating mode.
Programming is carried out with the programming software using a PC or laptop con-
nected to the fire panel.
The suitable response sensitivity of the multisensor detector is programmed by speci-
fying the operating location (e.g. computer room, office, large kitchen). The selection of
the operation location determines the optimal characteristic diagram for the fire and dis-
turbance variable evaluation.
If, according to the operating location, a low sensitivity is set for the optical sensor, the
alarm goes off only if the detector senses high levels of smoke and of CO at the same
time. This is the case with open or smouldering fire.
Programming the multisensor detector and linking all detectors by algorithms, consider-
ably increases the fire detection reliability and lowers the false alarm rate.
FAP−OC 500(−P)
Operating locations for multisensor detector
Operating locations for multisensor detector
(FAP−OC 500) selectable via the programming software
Office (smokers) / waiting room / restaurant / conference
room
Conference room / waiting room / exhibition hall
Warehouse with vehicle traffic
Production facilities
Kitchen / casino / restaurant during operation
Garage
Office (daily operation)
School / kindergarten
Theaters / concert halls
Office (no traffic)
Computer room
High−board warehouse without vehicle traffic with internal
combustion engines
Page 12
PI − 34.70 en
Sensitivity
O unit
C unit
low
low
low
low
low
low
medium
medium
medium
high
high
high
BDL−F.01U.025.876
A5.en/ 02.02.2006
ST−FIR/PRM1 / zab