Bosch FAP-OC 500Series Product Information - Page 17

Browse online or download pdf Product Information for Oven Bosch FAP-OC 500Series. Bosch FAP-OC 500Series 40 pages. Built-in wall ovens
Also for Bosch FAP-OC 500Series: Installation Instructions Manual (21 pages), Instructions For Use Manual (40 pages), Installation Manual (6 pages), Installation Manual (28 pages), User Manual (48 pages), User Manual (48 pages), Installation Manual (28 pages), Use And Care Manual (44 pages), Installation Manual (32 pages), Use And Care Manual / Installation Instructions (40 pages), Quick Reference Manual (4 pages), Use And Care Manual (27 pages), Installation Manual (24 pages), Installation Manual (32 pages), Use And Care Manual (24 pages), Installation Manual (28 pages), Service Manual (41 pages), Use And Care Manual (21 pages), Installation Manual (32 pages), Service Manual (36 pages), Installation Manual (32 pages), Quick Start And Safety Manual (13 pages)

Bosch FAP-OC 500Series Product Information
Product Information 500 Series LSN Fire Detectors (EU)

5. Mounting Notes

The 500 series detectors may only be installed with an FAA−500
series detector base in combination with a FAA−500−BB ceiling
mount back box or an FAA−500−SB surface mount back box.

5.1. Ceiling Mount Back Box

The ceiling mount back box (Fig. 4.) is made of white
polypropylene.
It has four cable bushings with tightly−closing
rubbers lips of polyflam that are suitable for cable
diameters up to 1.4 cm.
When used with a base, approx. 30 cm of cable
length can be accommodated in the upper area of
the ceiling mount back box.
The false ceiling may have a maximum thickness of 32 mm.
Above the false ceiling, a free height of at least 11 cm is required.
D Bore a circular hole with a diameter of 130 mm (tolerance −1 mm to +5 mm) in the
false ceiling.
. A hole saw with
KOMET Metal Cutting Saws GmbH & Co. KG, Alte Str. 28, D−79576 Weil am
Rhein, Tel. ++49−7621−9783−0, www.komet.de
Fig. 5.: Plan view and side view of the ceiling mount back box FAA−500−BB
5.
Pos. Description
1
Cable duct connection (UL only)
2
Bracket
3
Screws for fastening base
4
Cable bushing
133 mm can be obtained from:
1
2
3
4
Page 17
PI − 34.70 en
4.
1/2 in. conduit (UL only)
129 mm
BDL−F.01U.025.876
A5.en/ 02.02.2006
ST−FIR/PRM1 / zab