Figure 4: Burner air inlet orientation
In order to ensure the accuracy of the orifice plate measurement, the burner air and gas
inlet positions must ensure that there is a straight pipe section of 5 times the pipe
diameter and no other resistance components;
The burner is equipped with a spark plug with cooling air, and the cooling air interface
is a Ø8 connection. It is recommended to use a metal tubing to take the combustion air
from the upstream of the air shut-off valve.
3. Burner operation requirement
The excess air coefficient of this series of burners must be ensured to be above 1.05,
and cannot be running at gas rich mode;
According to the actual situation on site, regularly maintain the burner, check and clean
the burner, recuperator and spark plug;
Regularly check the burning status of the burner, and track the flue gas data of the
burner to avoid damage to the burner due to abnormal combustion
The burner can run at pulse control, with turn down ratio 2:1; while running at
modulation control, the turn down ratio is 3:1.
The working temperature varies by recuperator material, please refer Table 3.
Recuperator Material
Anderson Thermal Soluions(Suzhou)Co. Ltd.
Anderson Thermal Solutions – ANM75 Burner Operation Manual
Table 3 Working temperature
Metal
SiC
Figure 5: Gas inlet orientation
Max. Working temperature(°C)
1150
1300