Daikin 2M56GV1G Service Manual - Page 6

Browse online or download pdf Service Manual for Chiller Daikin 2M56GV1G. Daikin 2M56GV1G 19 pages. 5.6 kw class outdoor unit, removal procedure

Daikin 2M56GV1G Service Manual
Removal of Electrical Component ASSY
Step
3
Cut the clamp.
4
Disconnect the
connector for the
outdoor temperature
thermistor [S7] from the
PCB.
5
Unhook the sealing
material of the fan
motor lead wire from
the hook.
6
Disconnect the relay
connector for the fan
motor.
4
Procedure
[S7]
Sealing material
Points
(R10770)
(R10771)
The sealing material should
be mounted as below.
Sealing material
(R11167)
(R10772)
Removal Procedure
Si11-990
40±5
(R11166)