Removal of Electrical Component ASSY
Step
3
Cut the clamp.
4
Disconnect the
connector for the
outdoor temperature
thermistor [S7] from the
PCB.
5
Unhook the sealing
material of the fan
motor lead wire from
the hook.
6
Disconnect the relay
connector for the fan
motor.
4
Procedure
[S7]
Sealing material
Points
(R10770)
(R10771)
The sealing material should
be mounted as below.
Sealing material
(R11167)
(R10772)
Removal Procedure
Si11-990
40±5
(R11166)