Installing the NEMA 4X Panel Gasket
ET 3170 Terminal
Intended use
When properly installed using the materials provided, and
according to these instructions, the NEMA 4X panel gasket
is intended to provide a NEMA 4X/IP66 seal between the
panel and the terminal for the ET 3170 terminal .
Product safety information
Read and understand all safety information in this
document before installing and using the NEMA 4X panel
gasket.
WARNING
To reduce the risks associated with electric shock or fire which,
if not avoided, may result in death or serious injury and/or
property damage:
Follow all product and accessory installation instructions.
!
Any servicing or other procedures not described in this
!
document are to be performed only by 3M Touch Systems
service personnel.
WARNING
To reduce the risks associated with electric shock or fire which,
if not avoided, could result in death or serious injury and/or
property damage:
Wiring installation should be done by a journeyman electrician
!
and must comply with federal and local electrical codes.
Properly install the ET unit with a NEMA 4X gasket that is
!
undamaged and effective.
WARNING
To reduce the risks associated with electrical shock which, if not
avoided, may- result in death or serious injury or property
damage:
Install the NEMA 4X panel gasket properly in order to achieve a
!
NEMA 4X seal on the front bezel.
Equipment
Materials supplied
Package contents
!
!
!
!
!
Tools required
!
Steps
1. Use the gasket as a template to position the cutout (or
2. Mark the position and dimensions of the cutout and
3M Touch Systems Proprietary Information
1
CAUTION
To reduce the risks associated with fire that may result in
personal injury or property damage:
Provide a minimum of 1 inch (25.4 mm) clearance behind the
!
ET unit for proper air circulation. In warm working environments,
this depth should be increased to provide better air circulation.
12 Phillips 10-32 by 3/4 inch screws
12 Phillips 10-32 by 1/2 inch screws
12 flat washers
12 lock washers
1 gasket
Phillips No. 2 torque screwdriver
use a full-scale cutout template, if your ET unit came
with one). Tack or tape the gasket (or template) onto
the panel where you want to mount the unit.
dimensions of screw holes on the panel.
Cutout dimensions are:
Width: 12.06 inches (306.32 mm)
!
Height: 10.66 inches (270.76 mm)
!
Depth: 5.25 inches (133.4 mm)
!