Installing the NEMA 4X Hatch
ET 350 Monitor (Models ET 350R and ET 350L3) and ET 3170 Terminal

Intended Use

When properly installed using the materials provided, and
according to these instructions, the NEMA 4X hatch is
intended to provide a NEMA 4X/IP66 seal on all sides for
TM
the 3M Dynapro
ET 350 monitor (specifically, ET 350R
and ET 350L3 monitors) and the ET 3170 terminal. The
ET 350L3 monitor is also UL Listed for use in Pollution
Degree 3 environments.
Product safety information
Read and understand all safety information in this
document before installing and using the NEMA 4X hatch.
WARNING
To reduce the risks associated with electric shock or fire
which, if not avoided, may result in death or serious injury
and/or property damage:
Follow all product and accessory installation instructions.
!
Any servicing or other procedures not described in this
!
document are to be performed only by 3M Touch Systems
service personnel.
WARNING
To reduce the risks associated with electric shock or fire
which, if not avoided, could result in death or serious injury
and/or property damage.
Wiring installation should be done by a journeyman electrician
!
and must comply with federal and local electrical codes.
Properly install the ET unit with a NEMA 4X gasket that is
!
undamaged and effective.
Properly install the ET unit so that it is environmentally sealed to
!
the NEMA 4X/IP66 standard. Do not use an ET unit that is not
rated for NEMA 4X/IP66 in environments that require such a
seal.
3M Touch Systems Proprietary Information
1
WARNING
To reduce the risks associated with electric shock or fire
which, if not avoided, could result in death or serious injury
and/or property damage.
Choose fittings and a power cable that provide adequate strain
!
relief for communications and power cables.
A cable/fitting combination will have to be found that meets local
!
electrical requirements and the requirements for a NEMA 4X
seal.
When connecting power with fixed field wiring, the power cable
!
must be double insulated. A clear, flexible insulator (supplied)
must cover the portion of the cable that is not double insulated
when connecting to a terminal strip connector.
When closing the hatch of the ET unit, make sure that it closes
!
flush and that the hatch screws do not bind when they are
attached. If the hatch is not closed properly, the NEMA 4X seal
may be compromised and the warranty invalidated.
CAUTION
To reduce the risk associated with electric shock or fire that
may result in personal injury or property damage:
After making an opening for cables, make sure that there are no
!
metal shavings in the hatch.
Use round cables that fit the diameter range of the cable fitting,
!
as shown in Table A, to meet local electrical requirements and
the requirements for a NEMA-4X/IP66 seal.