3M Litmann Quality 3100 Instructions Manual - Page 9

Browse online or download pdf Instructions Manual for Medical Equipment 3M Litmann Quality 3100. 3M Litmann Quality 3100 16 pages. Mining cable splice kit
Also for 3M Litmann Quality 3100: Quick Start Manual (2 pages)

3M Litmann Quality 3100 Instructions Manual
6.7
If present, fold back grounds and ground check conductors and temporarily tape
to cable jacket with vinyl tape.
6.8
Select one conductor and cut conductor approximately 9" (230 mm). Match this
conductor with same color conductor on opposite end.
6.9
Rotate cable so conductor twist will match original cable lay as much as
possible.
6.10
Take next conductor in rotation and cut approximately 6" (150 mm) from end.
6.11
If present, remove color code and/or separator tape for length of phase.
6.12
Remove insulation from ends of conductors for one-half connector length if
using butt splices, or two connector lengths if using parallel splices.
6.13
Pencil insulation for approximately ½" (13 mm), sand smooth and clean with
solvent wipe.
78-8127-6830-3-C
Fold back grounds &
ground check conductors
Figure 18
9"
(230 mm)
6"
(150 mm)
Figure 19
9
12"
(305 mm)
½"
(13 mm)
Required connector length