Comtrol RocketLinx ES8108 Quick Installation Manual
WIRING THE ALARM RELAY OUTPUT
The ES8108 has a built-in alarm-relay for port link and power events
notifications. The relay contacts are normally open and remain open when
there is no failure event. The relay contacts close when there is a failure
event to notify.
The failure events are selectable and enabled using the DIP switch on the
ES8108. The relay contacts of the ES8108 are rated for a maximum of 0.5A at
24VDC.
1.
Insert positive and negative wires into V+ and V-.
2.
Tighten the wire-clamp screws to prevent the wires from coming loose.
WARNING - Exposure to some chemicals may degrade the sealing properties
of materials used in the sealed relay

SETTING THE DIP SWITCH

Switch
Status
1 to 8
ON
(Port)
OFF
9
ON
(Power)
OFF
Maximum 0.5A/24VDC
Alm
PW1
PW2
Alarm Control
port 1~8
Description
Enables port link down alarm for the corresponding port
Disables port link down alarm for the corresponding port
Enables the power failure alarm
Disables the power failure alarm