Concoa 830-9413 Installation And Operation Instruction Manual - Page 5
Browse online or download pdf Installation And Operation Instruction Manual for Control Unit Concoa 830-9413. Concoa 830-9413 8 pages. Relief valves

2. Install the 9400 series in a vertical position so the valve body is self-
draining. The inlet piping should be short as possible, with no elbows,
and equal to or greater than the size of the pressure relief valve inlet
connection.
3. The discharge piping should be equal to or greater than the size of the
pressure relief valve outlet connection so as to prevent backpressure
when relieving. The piping termination point must be in a safe location
and away from ignition sources. The termination point must be
positioned to prevent the accumulation of moisture. An appropriate
load-bearing device should support discharge piping, other than a
short tailpipe.
MAINTENANCE
The relief valve should be inspected every 12-18 months to ensure proper
working order. Depending on the service and the condition of the valve, the
inspection interval may be adjusted.