Anywire BS-H0317-1K Product Manual - Page 2

Browse online or download pdf Product Manual for Accessories Anywire BS-H0317-1K. Anywire BS-H0317-1K 9 pages. Anywireaslink system

[Connection Example]

You can select use of either a two-wire or four-wire terminal for the AnyWireASLINK according
to the load current.
This Products Guide describes a two-wire (non-isolated) terminal.
If the load current is small, using a two-wire (non-isolated) terminal allows for achieving
simpli ed wiring without a local power supply.
If you are prioritizing the sites of concentrated loads or the number of units connected,
hybridization with a four-wire (isolated) terminal, which supports local power supply, is also
possible.
Make sure to use a four-wire (isolated) terminal in the case of input and load driving using an
external power supply.
In the case of hybridization, refer to the Four-Wire (Isolated) Terminal Products Guide
separately.
■Connection example using a two-wire (non-isolated) terminal
Red: DP
Red: DP
AnyWireASLINK
master
Black:
Black: DN
DN
Red: DP
24V DC*
Black: DN
* Make sure to use a
2 4 V D C s t a b i l i z e d
Red: DP
power supply for the
power supply to be
connected.
Black: DN
Red: DP
* When complying with the
UL Standard, make sure
to use a 24V DC stabilized
Black: DN
power supply of "NEC
Class 2 Output."
Red: DP
Black: DN
Red: DP
Black: DN
General-purpose
cabtire cable
Dedicated at cable
1.25mm
(two-wire)
2
2P link connector is
convenient for
branching.
Total of
line
portions of DP, DN
is total length.
Black: DN
Red: DP
AnyWireASLINK terminator
One terminator should be connected to
BT0
the DP, DN terminal farthest from the AnyWireASLINK master.
Connect it correctly so as not to set the wrong polarity.
■Relationship between the size and length of
the transmission line and the supply current (Table 1)
Supply current on the transmission line (DP, DN)
Size of
the transmission
Total length
line (DP, DN)
50m or less
1.25mm
MAX 2A
2
0.75mm
MAX 1.2A
2
0.5mm
MAX 0.8A
2
- Refer to Table 1 so that the size and length of the transmission
CAUTION
line and the allowable supply current lie within an appropriate
range.
- Connect the same symbols (DP, DN) correctly between the
AnyWireASLINK master and each device.
- The branching length or branch number has no limitation.
- Include the length of the cable provided with the terminal in the "total line length."
- Connect the terminator "BT0 (polar)" to the terminal on the transmission line farthest from
the AnyWireASLINK master.
Two points
Object to be
detected
Recurrent
re ection type
ASLINKAMP
Independent use
ASLINKAMP
Independent use
ASLINKAMP
Expansion use
ASLINKAMP
Expansion use
Transmission type
Black: DN
Two points
Red: DP
The branching
has no limitation.
Two points
Red: DP Black: DN
Total length: Over 50 m,
Total length: Over 100 m,
no longer than 100 m
no longer than 200 m
MAX 1A
MAX 0.5A
MAX 0.6A
MAX 0.3A
MAX 0.4A
MAX 0.2A
■Example of mixture of 2-wire (non-insulation), 4-wire (insulation) terminals
AnyWireASLINK
master
ASLINK lter
General-purpose power supply lter
24V DC*
Dedicated at cable
1.25mm
(four-wire)
2
4P link connector is
convenient for
branching.
Two points
Total of
line
portions of DP, DN
is total length.
24V DC*
Black: DN
CAUTION
-BSH03171K 2/8-
Red: DP
Red: DP
Two points
Black:
Black: DN
DN
Red: DP
Two points
Black: DN
Red: DP Black: DN
Red: DP
Recurrent
re ection type
Black: DN
Red: DP
Black: DN
Red: DP
Black: DN
Red: DP
Black: DN
Red: DP
Black: DN
Transmission type
The branching
has no limitation.
Red: DP
AnyWireASLINK terminator
One terminator should be connected to
BT0
the DP, DN terminal farthest from the AnyWireASLINK master.
Connect it correctly so as not to set the wrong polarity.
In the case of connection to a load (e.g. input/output port)
controlled by a different power supply than that used in the
AnyWireASLINK, make sure to use a four-wire (isolated)
terminal. Otherwise, a malfunction may occur.
Eight points
Object to be
detected
ASLINKAMP
Independent use
ASLINKAMP
Independent use
ASLINKAMP
Expansion use
ASLINKAMP
Expansion use
Eight points
Black: DN
Two points
Red: DP
Two points
Red: DP Black: DN
Two points