Also for Danfoss VLT HVAC Drive FC 102: Operating Manual (16 pages), Installation Manual (20 pages), Installation Instructions Manual (6 pages), Installation Manual (18 pages), Installation Instructions Manual (11 pages), Installation Instructions Manual (8 pages), Installation Instructions Manual (10 pages), Installation Manual (6 pages), Operating Instructions Manual (16 pages), Installation Instructions Manual (6 pages), Installation Manual (16 pages), Installation Manual (8 pages), Instruction Manual (16 pages), Installation Instructions Manual (6 pages), Installation Manual (6 pages)

Danfoss VLT HVAC Drive FC 102 Installation Instructions Manual
Installation Instructions
5.
Install the left and right brake terminals onto the brake terminal bracket using 4 M5 nuts. Torque to 2.3 Nm (20 in-lb).
6.
Secure the brake terminal assembly to the mains bus bar support with 2 M8 nuts. Torque to 9.6 Nm (85 in-lb). Refer to
Illustration 1.6.
7.
Assemble the mains bus bar subassembly using 9 stand-offs and 9 M5 nuts. Torque to 2.3 Nm (20 in-lb).
Refer to Illustration 1.8.
1
Mains bus bar support bracket
2
Stand-offs (front and back side of bus bar), indicated by an S in
the drawing
3
Slotted opening for M10 screw
Illustration 1.8 Assembling the Mains Bus Bar Subassembly
6
Bus Bar Kit for 6-pulse, 2-drive System
VLT® Series FC 102, FC 202, and FC 302
4
M5 nut
5
Brake terminal assembly (terminals and bracket)
6
Solid mains bus bars
Danfoss A/S © 02/2016 All rights reserved.