Danfoss ECL Comfort 110 User Manual, Installation & Maintenance
Introduction
How to use this guide
The instructions is divided into six parts:
• Introduction
• Settings overview
• Daily use
• Maintenance
• Installation
• Check
Basic principles of application 116 for ECL Comfort 110
If the measured flow (DHW) temperature (S3) is lower than the desired DHW
temperature, the motorized control valve (M1) is opened gradually and vice versa.
The return temperature (S4) to the district heating supply should not be too high. If so,
the desired flow temperature can be adjusted (typically to a lower value) thus resulting
in a gradual closing of the motorized control valve, i.e. the return temperature will
decrease.
The circulation pump, P1, is ON when the desired flow temperature is higher than 20 °C
(factory setting) or the actual flow temperature (S3) is below 10 °C (factory setting).
°C (degrees Celsius) is an absolute temperature whereas K (Kelvin) is a relative temperature.
6
Settings overview
Temp. min. (flow temp. limit, min.)
Temp. max. (flow temp. limit, max.)
Code no.
Ver. (version no.)
Backlight (display brightness)
Contrast (display contrast)
Language
MOD address (MODBUS address)
VI.KT.F2.02
Factory
Your
Line Page
setting
setting
2177
11
10 °C
2178
11
90 °C
4030 12
50 °C
4035 13
0.0
4036 14
0.0
4037 14
25 s
15
16
16
50 K
16
20 s
16
15 s
17
3 K
18
18
OFF
18
10 °C
18
20 °C
7093 19
10 °C
19
OFF
19
3
20
ON
20
15
7600 21
116
8300 22
XXXX
8301
22
XXXX
8310
22
16
8311
22
10
8315
23
English
8320 23
5
7