Also for Danfoss ECL Comfort 310: Installation Manual (8 pages), Mounting Manual (4 pages), User Manual (12 pages), User Manual (12 pages), Installation Manual (4 pages), Installation Manual (16 pages), Installation Manual (20 pages), Operating Manual (8 pages), Operating Manual (16 pages), Operating Manual (10 pages), Installation Manual (20 pages), Installation Manual (7 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (20 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (20 pages), Installation Manual (12 pages), Mounting Manual (20 pages), Mounting Manual (20 pages), Mounting Manual (12 pages), Mounting Manual (16 pages), Operating Manual (8 pages)

Danfoss ECL Comfort 310 Service Manual
Service guide

4.0 Modbus network definitions

4.1 Multipoint serial bus infrastructure

The below drawing gives a general overview of the serial bus
infrastructure in a Modbus multipoint serial line system.
1) = surge protector
The following conventions are adopted in the figure above:
1. The interface with the trunk is named ITr (Trunk Interface)
2. The interface between the device (ECL 296 / 310) and the
Passive Tap ( surge protector) is named IDv (Derivation
Interface)
3. The interface between the device (ECL 296 / 310) and the
Active Tap (repeater) is named AUI (Attachment Unit Interface)
4. LT = line termination. Resistor: 120 ohm , 0,5 W or 150 ohm,
0,5 W
A multipoint Modbus serial line bus is made of a principal cable
(the trunk) and possibly some derivation cables.
Line terminations are necessary at each extremity of the trunk
cable for impedance adaptation.
VI.LV.H1.02
ECL 296 / ECL 310 Modbus
2) = repeater
© Danfoss | 2017.06 | 3