Parameter 4 – Backlight
The backlight parameter allows the backlight to be
always on, always off , or on for 15 seconds after the
last key press.
Press + until parameter 4 is displayed.
GB
Press V or Λ to select the required setting.
0 = backlight always off
1 = backlight on for 15 seconds after the last key press (default)
2 = backlight always on
Parameter 5 – Number of events per day
This parameter sets the unit to operate with 4 or
6 events per day. An event being an ON or an OFF
period of room heating and/or hot water heating.
Press + until parameter 5 is displayed.
Press V or Λ to select the required setting.
WARNING: Changing this parameter will reset event
times to default values.
2 = 2 ON/OFF periods per day
3 = 3 ON/OFF periods per day (default)
Parameter 6 – Operating Mode
(7 Day, 5+2 Day or 24 Hour)
This parameter sets the unit to operate using either 7
day, 5+2 day or 24 hour mode.
Press + until Option 6 is displayed.
Press V or Λ to select the required setting.
WARNING: Changing this parameter will reset event
times to default values.
24 = 24 hour
5-2 = 5+2 Day (or A+B if set in parameter 1)
7 = 7 day (default)