Also for Danfoss VLT AutomationDrive FC 302: Operating Manual (16 pages), Installation Manual (20 pages), Installation Instructions (4 pages), Installation Instructions Manual (6 pages), Installation Instructions Manual (12 pages), Installation Manual (18 pages), Installation Instructions Manual (8 pages), Installation Instructions Manual (10 pages), Installation Manual (6 pages), Installation Manual (16 pages), Operating Instructions Manual (16 pages), Installation Instructions Manual (6 pages), Installation Manual (8 pages), Installation Instructions Manual (6 pages), Installation Manual (6 pages)

Danfoss VLT AutomationDrive FC 302 Installation Manual
Installation Guide | VLT® Programmable I/O MCB 115
Temperature sensor (1000 Ω at 0 °C
(32 °F)
Accuracy
Temperature range
Resolution [bits]
Sampling [Hz]
Maximum load
Impedance
Maximum cable length for temperature sensors is 50 m (164 ft) non-shielded/non-twisted wires.
-
Keep cable impedance low as every 3.85 Ω in cables gives a misreading of 1 Kelvin.
-

3.4.1.2 Programmable Outputs

The 3 programmable outputs can work as:
analog voltage outputs.
analog current outputs.
digital outputs.
Table 3: Programmable Outputs
Used as digital output
Number of outputs
3
Terminal
X49/7–12
Voltage/current range
Accuracy
Resolution [bits]
Maximum load
Load impedance
12 | Danfoss A/S © 2020.01
Used as temperature sensor
input
Ni1000 (according to DIN 43760)
Pt1000 (according to IEC 60751)
-50 °C ±1 Kelvin
+150 °C ±2 Kelvins
-50 °C (-58 °F) to +150 °C
(+302 °F)
10
3
Maximum voltage at low output: 4 V
Minimum voltage at high output: 20 V
Maximum output current: 24 mA
Used as analog voltage
input
Better than 1% of full scale
10
Minimum 2
±28 V continuously
10 kΩ
N O T I C E
Used as analog voltage output
3
X49/7–12
0–10 V DC
Better than ±1%
10
±28 V continuously
≥10 kΩ
Installation
Used as current input
Better than 1% of full
scale
10
Minimum 2
±29 mA continuously
200 Ω
Used as current output
3
X49/7–12
0–20 mA
Better than ±1%
10
±29 mA continuously
≤200 Ω
AN295938195323en-000101 / 130R0655