Data Aire DAP III Instructions Manual - Page 8

Browse online or download pdf Instructions Manual for Security System Data Aire DAP III. Data Aire DAP III 13 pages. Bacnet integration

Data Aire, Inc. DAP
Object Name
Temperature Sensor Problem
Maintenance Due
High Pressure / Internal
Overload: Compressor 1
Low Pressure C1
High Pressure C2/ Internal
Overload: Compressor 2
Low Pressure C2
Smoke Detector
(Optional)
No Water Flow
(Optional)
Discharge Air Sensor Problem
(Optional)
High Temperature Warning
Low Temperature Warning
High Humidity Warning
Low Humidity Warning
Fan Motor Overload
(Optional)
Local Alarm 1 (Optional)
Local Alarm 2 (Optional)
Local Alarm 3 (Optional)
Local Alarm 4 (Optional)
Standby Pump On
(Optional)
UPS Power On
(Optional)
Custom Alarm 1
(Optional)
Engineering Document - 600-000-460
TM
III BACnet Integration Instructions
Instance
Object Description
No. BV
18
Faulty Return Air temperature sensor
detected
19
The blower runtime has elapsed the
scheduled maintenance hours
20
Compressor #1 high pressure switch or
compressor internal overload relay trips
21
Compressor #1 low pressure switch
opens
22
Compressor #2 high pressure switch or
compressor internal overload relay trips
23
Compressor #2 low pressure switch
opens
24
Smoke Detected, unit shutdown. An
optional smoke detector required
25
Loss of water on calling for cooling, An
optional Water Flow switch required.
26
Faulty Discharge Air temperature sensor
detected. An optional temperature
required
27
The Return Air temperature rises above
the high temperature alarm limit setting
28
The Return Air temperature drops below
the low temperature alarm limit setting
29
The Relative humidity rises above the
high humidity alarm limit setting
30
The Relative humidity drops below the
low humidity alarm limit setting
31
The optional fan motor overload trips.
32
The optional alarm input 1 is
programmed to Local alarm #1: See tag
inside door and the alarm signal is active
33
The optional alarm input 2 is
programmed to Local alarm #2: See tag
inside door and the alarm signal is active
34
The optional alarm input 3 is
programmed to Local alarm #3: See tag
inside door and the alarm signal is active
35
The optional alarm input 4 is
programmed to Local alarm #4: See tag
inside door and the alarm signal is active
36
The optional alarm input is programmed
to Standby pump on: Check primary
pump and the alarm signal is active
37
The optional alarm input is programmed
to UPS power on: Check main power
supply and the alarm signal is active
38
The optional alarm input 1 is
programmed to Custom alarm #1 and the
alarm signal is active
Page 8 of 13
Present-
Value
Writeable
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No