Data Aire DAP III Instructions Manual - Page 9
Browse online or download pdf Instructions Manual for Security System Data Aire DAP III. Data Aire DAP III 13 pages. Bacnet integration
Data Aire, Inc. DAP
Object Name
Custom Alarm 2
(Optional)
Custom Alarm 3
(Optional)
Custom Alarm 4
(Optional)
Humidification Inhibited
(optional)
Reheat Inhibited
(Optional)
Reheat And Humid. Inhibited
(Optional)
Low Discharge Air Temperature
Alarm
(Optional)
Manual Override
High Condensate water level
(Optional)
Unit In Standby, All Functions
Held Off Alarm (Optional)
Cooling Inhibit
Heating Inhibit
Humidification Inhibit
Dehumidification Inhibit
Blower Inhibit
Engineering Document - 600-000-460
TM
III BACnet Integration Instructions
Instance
Object Description
No. BV
39
The optional alarm input 2 is
programmed to Custom alarm #2 and the
alarm signal is active
40
The optional alarm input 3 is
programmed to Custom alarm #3 and the
alarm signal is active
41
The optional alarm input 4 is
programmed to Custom alarm #4 and the
alarm signal is active
42
The optional inputs are programmed to
Humidification inhibited and the input
signal is active
43
The optional inputs are programmed to
Reheat inhibited and the input signal is
active
44
The optional inputs are programmed to
Reheat and Humidification inhibited and
the input signal is active
45
The Discharge Air temperature drops
below the low discharge temperature
setting limit. An optional Discharge Air
temperature sensor required
46
Manual override switches are on; unit
operates in the manual control mode.
47
High condensate water level switch of
the optional condensate pump closes.
This is a standard alarm on ceiling units.
48
The optional alarm input 1 is
programmed to Unit in standby, all
functions held off and the alarm signal is
active. Unit is put to standby mode.
1001
The Cooling stages will be inhibited
when this point is on.
1002
The Heating stages will be inhibited
when this point is on
1003
The Humidification function will be
inhibited if this point is on
1004
The dehumidification function will be
inhibited if this point is on.
1005
The blower(s) will stop if this point is
on. In a normal circumstance, this point
should be off at all time
Page 9 of 13
Present-
Value
Writeable
No
No
No
No
No
No
No
No
No
No
Yes-
Enumerated
(0,1)
Yes-
Enumerated
(0,1)
Yes-
Enumerated
(0,1)
Yes-
Enumerated
(0,1)
Yes-
Enumerated
(0,1)