Datakom DFC-0108 Installation Manual - Page 4
Browse online or download pdf Installation Manual for Controller Datakom DFC-0108. Datakom DFC-0108 8 pages. Power factor controller 8 banks, harmonic distortion
Holding the
switches between TEST and MANUAL modes
In TEST mode, if no button is pressed during 1 minute the
unit will automatically return back to MANUAL mode.
In TEST mode only the total kVAr value is displayed.
When TEST mode is selected then the step-1 indicator led will flash. Pressing the
pushbutton will activate this step. Pressing the
Pressing the
flash. Using
Using the
MENU pushbutton all steps may be scrolled manually.
TEST MODE, MANUAL STEP CONTROL
pushbutton pressed for 5 seconds
MENU pushbutton will select the next step and the related step led will
pushbuttons the step may be activated or deactivated.
pushbutton will deactivate this step.