Datakom DPR-145 User Manual - Page 14
Browse online or download pdf User Manual for Relays Datakom DPR-145. Datakom DPR-145 19 pages. Temperature protection relay
DPR-145 User Manual
DISPLAY
DESCRIPTION
FAULT RELAY TEST ()
Used to test the FAULT relay. The value
of "1" activates the relay. The value of
"0" deactivates it.
ALARM RELAY TEST ()
Used to test the ALARM relay. The value
of "1" activates the relay. The value of
"0" deactivates it.
FAN RELAYE TEST ()
Used to test the FAN relay. The value of
"1" activates the relay. The value of "0"
deactivates it.
ALARM PARAMETER ()
Adjusts High Temperature Alarm limit
values of each channel.
TRIP PARAMETER ()
Adjusts High Temperature Trip values of
channels.
FAN CHANNEL PARAMETER ()
This parameter defines from which
channels the fan will operate.
0: none
1: channel_1
2: channel_2
3: channel_1+2
4: channel_3
5: channel_1+3
6: channel_2+3
7: channel_1+2+3
FAN ON PARAMETER ()
Adjusts Fan Turn ON Temperature
-14-
8: channel_4
9: channel_1+4
10: channel_2+4
11: channel_1+2+4
12: channel_3+4
13: channel_1+3+4
14: channel_2+3+4
15:
1+2+3+4
channel_
V-3.0
(14.09.2016)
MIN
MAX
0
1
0
1
0
1
0
295
5
300
0
15
5
300