Option "4"
Note (1):
In Ni-Cd. The End-of-charge is determined by negative ∆V detection of battery voltage (-5mV/cell). If no negative ∆V but
only a "flat" profile is detected fast charge is terminated after 10 min. General end-of-charge timeout set to 16 hours.
Trickle charge current is regulated at 10% of max current set by the trimmer on the front panel in position N°5. In order
to detect end-of-charge negative ∆V, charging current must be set at least at 30% of nominal battery capacity (0,3 C);
with lower values of charging current negative ∆V detection is not guaranteed.
Jumper Setting always active during all states of the system.
Functional Setting
Battery LIFE TEST
Caution: Switch off the system before Setting the Jumper.
Functional Setting
ENABLE POWER
SUPPLY
ENABLE POWER SUPPLY function
With this feature enabled, there is always voltage on the Output BATTERY even if is the battery is not present, in this
way you don't have voltage dips, the Battery Care is guaranteed but the controls on the battery are limited.
Be careful: don't reverse the battery polarity.
No. 19: Other Battery Management Configurations
Jumper Setting always active during all states of the system.
Functional Setting
FAST CHARGE
Enable
OPTION
No. 18: SELECTION OUT VOLTAGE
Caution: Switch off the system before Setting the Jumper.
Functional Setting
Output Voltage
selection
Output Voltage
selection
BATTERY TYPE
Do not use other configurations for Battery Management
LIFE TEST
ENABLE POWERSUPPLY
12 Vdc
24 Vdc
Function
ON position = LIFE TEST enabled
Function
ON position = function POWER SUPPLY
enabled
Function
Fast charge enabled. Only for Lead or Gel
battery.
Future implementation
Function
12V Output Voltage
24V Output Voltage
Default setting