5. Route the wires from the wire conduit(s) through the conduit fitting(s) and
into the housing.
6. Thread the wire conduit tightly into the conduit fitting ensuring a water-
tight seal. If necessary, seal with silicone or equivalent caulking (not
provided) to prevent water from leaking into the cabinet.
FAILURE TO ENSURE A WATER-TIGHT
INSTALLATION OF THE CONDUIT AND
WARNING:
FITTING(S) WILL VOID THE MANUFACTURER
WARRANTY.
7. Connect AC wires from building utility: install the ground wire.
a. Standard unit: connect the transformer primary wires to the utility:
white wire to neutral; black (120Vac) or orange (277Vac) to line
voltage (See figure 3).
Remote emergency lighting (option): connect the remote DC wires to the
terminals of lamp circuit (Figure 3).
LED EMERGENCY LIGHTS HAVE POLARIZED
WARNING:
WIRES: OBSERVE POLARITY L+ AND L– FOR
LOAD CONNECTION.
b. RFI (option): Connect output line (black) from RFI filter to the
transformer primary: black (120Vac) or orange (277Vac). Connect
RFI filter module to the utility: white wire to neutral, black wire (120/
277Vac) to line (See figure 4).
Option cold-weather: An electric heater and a thermostat are used to control
the ambient temperature inside the equipment.
Connections for 120Vac line voltage (Figure 5):
a. Install three red clips (provided) one on the yellow wire (heater), and
white and black wires (transformer).
b. Connect white wire (heater) to clip of yellow wire (heater).
c. Connect red wire (heater) to clip of white wire (transformer).
d. Connect red wire (thermostat) to clip of black wire (transformer).
Thermostat
Red
White(Netural)
Black(120V)
Orange(277V)
Figure 5
Emergi-Lite®
Tel: (888) 552-6467
®
White
Red
Heater Pad
Yellow
Fax: (800) 316-4515
HP Series Battery Unit for hazardous locations
Orange(277Vac)
White(netural)
Black(120Vac)
Figure 3
{
White(Netural)
Green(ground)
RFI
Black(line)
120/277Vac
Connected
to PCBA
Figure 4
Maximum mounting height
as per UL924 standards
LED Lamp wattage
6 - Watts
10 - Watts
15 - Watts
www.emergi-lite.com
Blue DC-
Red DC+
DC wires
for remotes
White
(Netural)
Black(load)
White
(Netural)
Black
Orange
120Vac
277Vac
.
Maximum mounting height
30 Feet
50 Feet
60 Feet