5V Encoder Inputs Wiring Diagram

To prevent damage to P2-HSI 5V inputs,
do not exceed 6.8V or 30 mA on inputs
1A, 1A, 1B, 1B, 1Z, 1Z, 2A, 2A, 2B, 2B, 2Z, & 2Z.
Encoder with 5V
Line Drivers
A
D
A
B
Sensor
D
B
Belden 3105A shielded,
twisted pair,
low capacitance.
C
D
C
Tie shield to panel
ground this end.
6
www.productivity2000.com
24V Encoder Inputs Wiring Diagram
P2-HSI
1A 169 Ohm
1A
1B 169 Ohm
Sensor
1B
1Z 169 Ohm
1Z
Dead head shield this end.
5VDC to 24VDC
+
+
A
C
B
E
B
C
B
Belden 3105A shielded,
twisted pair,
E
low capacitance.
Z
C
B
E
Tie shield to panel
-
ground this end.
Tech Support 770-844-4200
P2-HSI
+1A 2K Ohm
-1A
+1B 2K Ohm
-1B
+1Z 2K Ohm
-1Z
Dead head shield this end.