Autonics krn100 series Instruction Manual
Browse online or download pdf Instruction Manual for Measuring Instruments Autonics krn100 series. Autonics krn100 series 2 pages. 100 mm hybrid recorder
Also for Autonics krn100 series: Instruction Manual (2 pages), Product Manual (3 pages), Manual (17 pages)
100mm Hybrid Recorder
KRN100 SERIES
I N S T R U C T I O N
Thank you for choosing our Autonics product.
Please read the following safety considerations before use.
Safety Considerations
※Please observe all safety considerations for safe and proper product operation to avoid hazards.
※Safety considerations are categorized as follows.
Warning
Failure to follow these instructions may result in serious injury or death.
Caution
Failure to follow these instructions may result in personal injury or product damage.
※The symbols used on the product and instruction manual represent the following
symbol represents caution due to special circumstances in which hazards may occur.
Warning
1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial
economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion
apparatus, safety equipment, crime/disaster prevention devices, etc.)
Failure to follow this instruction may result in personal injury, fire, or economic loss.
2. The unit must be installed on a device panel before use.
Failure to follow this instruction may result in electric shock.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock .
4. Do not disassemble or modify the unit. Please contact us if necessary.
Failure to follow this instruction may result in electric shock or fire.
5.Check the terminal numbers before connecting the power source.
Failure to follow this instruction may result in fire.
Caution
1. Do not use the unit outdoors.
Failure to follow this instruction may result in shortening the life cycle of the unit, or electric shock.
2. Use the unit within the rated specifications.
Failure to follow this instruction may result in shortening the life cycle of the unit, or fire.
3. Do not use water or oil-based detergent when cleaning the unit. Use dry cloth to clean the unit.
Failure to follow this instruction may result in electric shock or fire.
4. Do not use the unit where flammable or explosive gas, humidity, direct sunlight, radiant heat, vibration, or impact may
be present.
Failure to follow this instruction may result in fire or explosion.
5. Keep dust and wire residue from flowing into the unit.
Failure to follow this instruction may result in fire or product damage.
6. Check the polarity of the power contact before wiring the unit.
Failure to follow this instruction may result in fire or explosion.
※Please read "Safety Considerations" in KRN100 user manual before using.
Specifications
Series
KRN100
Power voltage
100-240VAC 50/60Hz
Allowable voltage range
85 to 110% of rated voltage
Power consumption
Max. 55VA
LCD type
STN Graphic LCD
Resolution
320×120 Pixel
Screen
Adjusting brightness
4-level (OFF/Min/Standard/Max)
Backlight
White LED, 2-level (Temp/Always)
Input channels
2 / 4 / 6 / 8 / 10 / 12-channel (2-channel/card)
Universal input
Temperature sensor (RTD, thermocouple), analog (voltage, current)
1 to 4-channel: 25ms/125ms/250ms, 5 to 12-channel: 125ms/250ms
Sampling period
(inner sampling period is operation unit time for average movement filter and alarm output function.)
※ Min. sampling period for TC-R, U, S, T sensor is 50ms.
Recording speed in graph mode
10, 20, 40, 60, 120, 240mm/H
Recording speed accuracy
F.S. ±0.5%
Storage cycle
1 to 3600 sec (storage interval time to inner log file is 1 sec)
Inner memory
512MB
USB memory
User purchased, recognizes max. 32GB, enables to use cable up to 1.5m
2500VAC 50/60Hz for 1 min (power terminal and case) ※ Excepts USB Device and Ethernet
Dielectric voltage
Vibration strength
Vibration strength: 10 to 60Hz 4.9m/s
(for convey and storage) and
Operating vibration: 10 to 60Hz 1m/s
operating vibration
Insulated resistance
Min. 20MΩ (at 500VDC megger)
Noise
±2kV the square wave noise (pulse width 1㎲) by the noise simulator
Time accuracy
Within ±2 min/year (enables to use up to 2100 year)
Enables to normal print with going and returning printing max. 5 times within 7 days after
Ink cartridge
Mech-
opening the unit
anism
Ink dry time
Max. 15 minutes
Protection
IP40 (for front panel)
Recording paper
113mm×9m
Ambient temperature
0 to 50℃, storage: -20 to 60℃ (without ink cartridge)
Environ-
ment
Ambient humidity
35 to 85%RH, storage: 35 to 85%RH
Approval
,
※ 1
Weight
Approx. 2.4 to 2.7kg (approx. 1.7 to 2.0kg)
※ 1: The weight includes packaging. The weight in parentheses is for unit only.
※ Environment resistance is rated at no freezing or condensation.
Dimensions
18.6
144
● Panel cut-out
Min.175
138
+1.0
0
※ Use a steel plate which is 2 to 8mm thickness.
※The above specifications are subject to change and some models may be discontinued without notice.
M A N U A L
2
(each X, Y, Z axis for 1 hour)
(each X, Y, Z axis for 10 min)
2
137
168
※ This rear side dimension is with
installed I/O cards to every slot.
Connections
This figure is the rear side of KRN100-04000-00-0S.
Slot
Description
1 to 6
Connects universal input card (KRN-UI2).
Connects digital input card (KRN-DI6), alarm output
7 to 10
card (KRN-AR4, KRN-AT6), transmitter power output
card (KRN-24V3).
C
Connects communication output card (KRN-COM).
l/O Card
Universal input card
[KRN-UI2]
-
+
-
+
※ Each channel is isolated and dielectric
strength is 500V.
Alarm output card
[KRN-AT6 (transistor output)]
Inner
Alarm Output
NPN Open
Collector
12-24VDC/
30mA Max.
RESISTIVE
LOAD
※ AL1,2,3 and AL4,5,6 are isolated.
Screen Layout And Status Display
Screen layout is divided as two; upper screen for status display, lower screen for measuring value display, virtual keyboard display,
parameter setting display.
Upper screen displays recorder status and information of recorder as icon.
Section
Icon
Name
Record start icon
Record stop icon
List record icon
1
Reservation record icon Flashes during reservation recording.
FEED icon
Backup data print icon
Digital mode icon
Graph mode icon
2
Record memory status
icon
No recording paper icon Marks it for no recording paper. Please replace new recording paper.
(unit: mm)
USB
communication icon
Ethernet communication
3
icon
RS485 communication
icon
4
Alarm ON icon
Digital input(DI) icon
Digital input(DI)-
memo icon
Digital input(DI)-
alarm reset icon
Digital input(DI)-
5
start record icon
Digital input(DI)-
stop record icon
Digital input(DI)-
LIST output icon
Digital input(DI)-
record speed icon
Unlock icon
User(general user)
6
lock icon
Administrator lock icon Marks it for administrator and general user lock status.
Inner and external (USB)
7
memory capacity icon
8
Date/Time display
Input Type Setting
Before setting the parameters, set the jumper pin channel 1/2 of
universal input card (KRN-UI2) depending on input specification
as below figure.
SOURCE
Ch1 Jumper
100-240VAC
50/60Hz, 55VA
F.G.
Ch2 Jumper
Jumper
Input
pin
specification
①
0 to 20mA, 4 to 20mA
②
TC, RTD, ±60mV, ±200mV Enables
③
±2V, 1 to 5V, ±5V, -1 to 10V Disables
User Manual
For the detail information and instructions, please refer to user
manual and user manual for communication.
Download manuals from the enclosed CD-ROM or our web site
(www.autonics.com).
Digital input card
[KRN-DI6]
[KRN-AR4 (relay output)]
Inner
Transmitter power output card
Communication output card
[KRN-24V3]
※ Each 24V output is isolated individually.
Description
Marks if for starting recording measuring value of recordable channels.
Stops recording measuring value.
Flashes during list recording.
Flashes during feeding recording paper.
Flashes during backup data printing.
Marks it for digital record mode.
Marks it for graph record mode.
Marks it storage capacity of record memory in digital mode or graph mode.
Marks
icon during Modbus RTU communication using USB.
Marks
icon during Modbus TCP communication using Ethernet.
Marks
icon during Modbus RTU communication using RS485.
Marks
channel icon which alarm occurs.
Marks the below icon according to input function setting during digital input (DI).
Marks it when digital memo of digital input or front
status.
Marks it when alarm reset signal of digital input (DI) is input.
Marks it when start record signal of digital input (DI) is input.
Marks it when stop record signal of digital input (DI) is input.
Marks it when LIST output signal of digital input (DI) is input.
Marks it when changing record speed signal of digital input (DI) is input.
Marks it for unlock status.
Marks it for user (general user) lock status.
Displays data capacity of internal memory as bar graph.
Displays current date and time. In summer time season, (S) mark is also
displayed at front of year.
③ ② ①
Terminal
direction
Input break alarm
Enables only 4 to 20mA
Alarm output card
Alarm Output
Relay Contact
250VAC 3A 1a
RESISTIVE LOAD
[KRN-COM]
USB 2.0
(Mini B type)
RS485 A(+)
RS485 B(-)
RS485 S.G
10/100 Base-T
RJ45(Ethernet)
is input in recording