Autonics KRN1000 Series User Manual - Page 11
Browse online or download pdf User Manual for Measuring Instruments Autonics KRN1000 Series. Autonics KRN1000 Series 15 pages. Lcd touchscreen paperless recorder
Also for Autonics KRN1000 Series: Instruction Manual (2 pages), Instruction Manual (2 pages)
-|Transparent setting guide|-
KRN1000 Series
Functions
Internal Memory Info.
It sets number of events, alarms, screen captures, and
storage options at internal memory.
It sets also internal memory storage options. When internal
memory uses all, it operates overwrite (deletes oldest data)
or stop (stops saving).
Firmware update
Update firmware.
Download the firmware at our web site (www.autonics.com).
Save the downloaded firmware at the top-level folder on
USB/SD memory and touch [Menu]-[System Info.]-[System
Info.].
When completes firmware update, re-boot the unit.
Do not turn OFF the power during firmware update.
RS422/485 Communication setting
Setting items are only available to check by communication.
RS422/485 communication makes set or monitor parameters at external upper system (PC or graphic panel, etc.) and uses
transfer data. It is recommended to use our dedicated software program DAQMaster for monitoring.
If you want to develop monitoring program not using our DAQMaster program or to use the related Modbus program, please
refer to user manual for communication.
Visit our homepage (www.autonics.com) to download DAQMaster program, and user manual for communication.
Interface
Item
Application standard
Max. connections
Com. distance
※ 1
Com. method
Com. synchronization method
Com. speed
Com. response wait time
Start Bit
Data Bit
Parity Bit
Stop Bit
Protocol
※ 1. In case of Ethernet connection, and connecting through the network such as network hub (HUB) and gateway, etc, there is no distance
limit, but it is recommended to use min. network. Please use communication cables which is satisfied the below conditions.
· RS422/485 communication: Shield Twist Pair over AWG24, characteristic impedance 100Ω,
· Ethernet communication: Over CAT5E, cable max. length: 100m
· USB communication: Single cable built-in ferrite core within 1.5m
※ USB device is recognized as USB to Serial device and communication speed: 115200bps, start bit: 1-bit, data bit: 8-bit,
parity bit: none, stop bit: 1-bit are fixed.
Application of system organization
Computer
※ It is recommended to use Autonics communication converter; SCM-WF48 (Wi-Fi to RS485·USB wireless communication converter, sold
separately), SCM-US48I (USB to RS485 converter, sold separately), SCM-38I (RS232C to RS485 converter, sold separately).
Please use twisted pair wire, which is suitable for RS485 communication, for SCM-WF48 and SCM-US48I.
U-14
RS485
Compliance with EIA RS485
31 units
(address: 1 to 127)
Within max. 1km
(below 9600bps)
Full duplex / Half duplex
Asynchronous
2400/4800/9600/19200/38400bps
5 to 99ms
1-bit (fixed)
8-bit (fixed)
None, Odd, Even
1, 2-bit
Modbus RTU
capacity component 50 pF/m cable length max. 1km
RS232C/
USB/Wi-Fi
RS485
Comm.
converter
A (+) B (-)
B (-)
DEVICE
OFF
ON
A (+)
Ethernet Communication setting
It sets about Ethernet communications.
Set IP address, subnet mask, default gateway,
communication write, Ethernet port, USB communication
write, USB device usage.
Ethernet
-
1 unit
(number of occupations per a unit)
Single cable within 100m
(recommended over CAT5E )
Full duplex
Asynchronous
10/100Mbps
-
-
-
-
-
Modbus TCP
Terminating resistance
(100 to 120Ω)
A (+) B (-)
A (+) B (-)
RS485
RS485
RS485
DEVICE
DEVICE
#1
#2
USB
Compliance with USB V2.0
1 unit
Single cable within 1.5m
-
Asynchronous
12Mbps (full Speed)
-
-
-
-
-
Modbus RTU
B (-)
RS485
DEVICE
#31
A (+)
#30