■ MP5W
• Power / input terminal
2
3
4
5
6
1
0 V
INA
INB
0 V
HOLD / RESET
BANK
• A: relay quintuple output
CONTACT OUT:
250 VACᜠ 3 A, 30 VDCᜡ 3 A RESISTIVE LOAD
10
11
12
13
14
HH
H
GO
L
LL
COM
• 1: relay triple output
CONTACT OUT:
250 VACᜠ 3 A, 30 VDCᜡ 3 A RESISTIVE LOAD
H
GO
L
10
11
12
13
14
• 2: NPN open collector + BCD Dynamic output
MAIN OUT
Sub power
(NPN OPEN COLLECTOR)
+ 24 VDCᜡ
30 VDCᜡ 30 mA
30 mA Max.
HH
GO
LL
B
D
10
12
2
4
6
8
1
3
5
7
9
11
COM
H
L
A
C
0V
BCD OUT
(NPN OPEN COLLECTOR)
30 VDCᜡ 30 mA
• POL signal turns ON when the display value is a minus (-) value.
• 4: NPN open collector + PV transmission output
MAIN OUT
Sub power
(NPN OPEN COLLECTOR)
+ 24 VDCᜡ
30 VDCᜡ 30 mA
30 mA Max.
(+)
HH
GO
LL
2
4
6
8
10
12
1
3
5
7
9
11
COM H
L
0V
DC 4 - 20 mA / DC 0 - 20 mA
(Load 500 Ω Max.)
• 5: PNP open collector + PV transmission output
MAIN OUT
Sub power
(PNP OPEN COLLECTOR)
+ 24 VDCᜡ
30 VDCᜡ 30 mA
30 mA Max.
LL
HH
GO
10
12
2
4
6
8
1
3
5
7
9
11
COM H
L
0V
DC 4 - 20 mA / DC 0 - 20 mA
(Load 500 Ω Max.)
• 8: NPN open collector + RS485 comm.
Sub power
MAIN OUT
(NPN OPEN COLLECTOR)
+ 24 VDCᜡ
30 VDCᜡ 30 mA
30 mA Max.
HH
GO
LL
10
12
2
4
6
8
9
11
1
3
5
7
COM
H
L
0 V
• 9: PNP open collector + RS485 comm.
MAIN OUT
Sub power
(PNP OPEN COLLECTOR)
+ 24 VDCᜡ
30 VDCᜡ 30 mA
30 mA Max.
HH
GO
LL
10
12
2
4
6
8
1
3
5
7
9
11
COM H
L
0 V
7
8
9
+ 12 V
SOURCE
15
15
D1
D3
DOT COM2
14
16
18
20
13
15
17
19
D0
D2
D4
POL
14
16
18
20
13
15
17
19
(-)
(+)
14
16
18
20
13
15
17
19
(-)
RS485
B (-)
14
16
18
20
13
15
17
19
A (+)
RS485
RS485
B (-)
14
16
18
20
13
15
17
19
A (+)
RS485

Specifications

Series
MP5S
Solid state input 1: ≤ 50 kHz (pulse width: ≥ 10 ㎲)
Input signal
Solid state input 2
01)
Contact input: ≤ 45 Hz (contact: 12 VDCᜡ ≥ 5 mA, (pulse width: ≥ 11 ms)
Voltage input
Input impedance: 3.9 kΩ, [H]: 4.5 - 24 VDCᜡ, [L]: 0 - 1 VDCᜡ
Short-circuit impedance: ≤ 80 Ω, residual voltage: ≤ 1 VDCᜡ,
No-voltage input
open-circuit impedance: ≥ 100 kΩ
Display method
7-segment LED (zero blanking method)
Character size
W 4 × H 8 mm
Prescale
0.0001 × 10
to 9.9999 × 10
-9
Hysteresis
0 to 9999
03)
Display cycle
OFF
, 0.05, 0.5, 1, 2, 4, 8 sec (same as update output cycle)
04)
Display range
-19999 to 99999
Output
Depending on models
Relay
250 VACᜠ 3 A, 30 VDCᜡ 3 A resistive load
NPN / PNP open collector ≤ 30 VDCᜡ 30 mA
BCD Dynamic
NPN open collector ≤ 30 VDCᜡ 30 mA (Dynamic COM cycle (T) = 40 ms)
DC 4 - 20 mA (load: ≤ 500 Ω, resolution: 8,000 divisions) /
PV transmission
DC 0 - 20 mA (load: ≤ 500 Ω, resolution: 10,000 divisions)
RS485 communication
Modbus RTU
Product components
Product, instruction manual
Bracket
Mounted
Unit sticker
× 1
Unit weigth (package)
≈ 132 g (≈ 191 g)
ᜢ ᜧ ᜫ
Approval
01)  Standard duty ratio 1:1
02)  Operation mode F7, F8, F9, F10: ≤ 1 kHz (pulse width: ≥ 500 ㎲)
03)  The hysteresis setting range varies according to the decimal point setting position.
04)  Only available operation mode F2, F16
AC voltage
100 - 240 VAC ᜠ ± 10 %
Power supply
50 / 60 Hz
Power consumption
Depending on Series / power supply
MP5S
≤ 7.5 VA
MP5Y
≤ 9 VA
MP5W
≤ 15 VA
≤ 12 VDCᜡ ± 10 % 80 mA
External power supply
Sub power supply
≤ 24 VDCᜡ 30 mA
01)
Memory retention
Number of inputs: 100,000 operations (non-volatile semiconductor memory type)
Mechanical: ≥ 10,000,000 operations (switching frequency 180 operations / min)
Relay life cycle
Electrical: ≥ 100,000 operations (250 VACᜠ
load) (switching frequency 20 operations / min)
Insulation resistance
≥ 100 MΩ (500 VDCᜡ megger)
2,000 VACᜠ 60 Hz for 1 min
Dielectric strength
Noise immunity
±2 kV the square wave noise (pulse width: 1㎲) by the noise simulator
Vibration
0.75 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z
direction for 1 hour
Vibration
0.5 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z
(malfunction)
direction for 10 min
Shock
300m / s² (≈ 30G) in each X, Y, Z direction for 3 times
Shock (malfunction)
100m / s² (≈ 30G) in each X, Y, Z direction for 3 times
Ambient temperature
-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity
35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
01)  Only for MP5W
Operation mode
Measurement range
F1
Frequency / revolutions / speed
0.0005 Hz to 50 kHz
F2
Passing speed
F3
Cycle
F4
Passing time
0.01 to max. of each time
range
F5
Time interval
F6
Time differential
F7
Absolute ratio
F8
Error ratio
0.0005 Hz to 50 kHz
F9
Density
F10
Error
F11
Length measurement 1
F12
Interval
0 to 99999
F13
Accumulation
Addition / subtraction-
F14
individual input
-19999 to 99999
Addition / subtraction-phase
F15
difference input
F16
Length measurement 2
0 to 99999

Communication Interface

■ RS485
Comm. protocol
Modbus RTU (16-bit CRC)
Application standard
Compliance with EIA RS485
Max. connection
31-unit (address: 1 to 127)
Comm. synchronous method Asynchronous
Comm. method
2-wire half duplex
Comm. distance
≤ 800 m
Comm. speed
2,400 / 4,800 / 9,600 (default) / 19,200 / 38,400 bps
Comm. response time
5 to 99 ms (default: 20 ms)
Start bit
1-bit (fixed)
Data bit
8-bit (fixed)
Parity bit
None (default), Even, Odd
Stop bit
1-bit, 2-bit (default)
MP5Y
MP5W
: ≤ 5 kHz (spulse width: ≥ 100 ㎲)
02)
W 7 × H 14 mm
9
× 2
× 2
× 1
× 2
≈ 140 g (≈ 230 g)
≈ 210 g (≈ 334 g)
AC / DC voltage
24 VACᜠ ± 10 % 50 / 60 Hz,
24 - 48 VDCᜡ ± 10 %
AC: ≤ 6 VA, DC: ≤ 4.5 W
AC: ≤ 7 VA, DC: ≤ 6.2 W
AC: ≤ 11 VA, DC: ≤ 7 W
3 A
3 A
, 30 VDCᜡ
Measurement accuracy
(23 ± 5 ℃)
F.S. ± 0.05 % rdg ± 1 digit
F.S. ± 0.01 % rdg ± 1 digit
F.S. ± 0.05 % rdg ± 1digit
-
resistive