The procedure allows to restore the XWEB to the factory parameters; it is useful in cases where the IP
address and / or port of the web service and / or login credentials (username / password) have been lost and
/ or in the presence of generic errors.
Function activated by pressing the button for a long time.
While the button remains pressed, the Cleanout procedure starts.
The progress of the procedure is intuitive thanks to the flashing of the LEDs:
1. Press the button
2. The two LEDs flash for ~ 5 seconds (Green)
3. The two LEDs remain steady for ~ 1 second (Green)
4. The two LEDs turn OFF
5. Release the button
6. The Cleanout starts and a reboot is triggered.
Throughout the procedure, then pressing the button takes about 6~7 seconds.
When restarting, you will find the Wizard active and System Settings preserved.
8.
OPERATIVE PROCEDURES
For the operating procedures please refer to the OPERATING MANUAL, in the "Download Manuals" section