Also for Emerson E2: User Manual (17 pages), Quick Reference Manual (2 pages), Quick Setup Manual (2 pages), Quick Start Manual (8 pages), Instruction Manual (12 pages), Quick Start Manual (14 pages), Quick Start Manual (14 pages), Quick Start Manual (9 pages), Installation And Operation Manual (20 pages), Technical Bulletin (8 pages)

Emerson E2 Quick Start Manual
5. After pressing T4 (ENTER) the screen below appears. Press T8 (right arrow) to move to the next
screen.
6. Verify if the address is defaulted at 1. If you need to change the default address, press T5 (down
arrow) and highlight the MODBUS address number. Once the address number is highlighted, press T4
(SET), and the number should blink. Press T3 to increase the address number or T4 to decrease the
address number. After the address number is selected, press T4 (SET) to exit, then press T1 (EXIT)
twice to exit the Configuration mode. If the address is changed, the High Pressure CO2 needs a
manual reboot for the new address to take place.