2iB SC10 Installation And User Manual - Page 6
Browse online or download pdf Installation And User Manual for Controller 2iB SC10. 2iB SC10 16 pages. Single pump controller
Also for 2iB SC10: Quick Start Manual (5 pages)
5.7
Current Window Setting
See section 4.1 Snoring Detection Explained for an explanation of the
Current Window.
The current window setting has 4 dip switches +2%, +4%, +8% and +16%,
by selecting a current window it adds the percentage to the stop current
setpoint.
As an example if the stop current threshold is set to 20% of CT range and
the window current is set to +4% via dip switch 13 the stop current
threshold = 20% + 4% = 24 % of CT range.
Single Phase Motors. See also the note about single-phase motors in
section 4.1 Snoring Detection Explained.
5.8
Current Setpoint Adjustment
An additional adjustment method is by using the up () and down () buttons independently. By
pushing the up or down button it will adjust the stop current threshold to the user's desired value as
a percentage of CT current.
Note: This settings is non-volatile. It is stored through power-cycles of the SC10.
6.
Display and LED Indication
6.1
Current % Display
PA = PAUSING. Pump is Pausing.
CL = CLEANING. Pumps is Stopped for a Cleaning flush.
Number = the measured current as a percentage of the measured range. (Taking into account the Current Transformer range
configured using the DIP switches as per section 5.1.)
6.2
LED Indicators
See section 12 Reference for details of the LED indicators.
6
Current Window (%)
SW
Setting
11
On: +16%
12
On: +8%
13
On: +4%
14
On: +2% (default)