2iB SC10 Quick Start Manual - Page 3
Browse online or download pdf Quick Start Manual for Controller 2iB SC10. 2iB SC10 5 pages. Single pump controller
Also for 2iB SC10: Installation And User Manual (16 pages)
Function of the buttons:
The 2iB SC10 is usually used as a Snore Controller. A pump snores (sucks air / stops pumping) when the water level drops too low.
When this happens the current drawn by the pump motor will drop. These buttons allow adjustment of the current at which
snoring and detected and the pump stops. The snoring and thus stop current varies depending upon the pump and its hydraulic
system and so often requires adjustment on-site.
Auto-Set: Press this button when the pump is snoring and the SC10 will automatically adjust the Stop Current based on
Up and Down: These allow the current setpoint to be manually adjusted up and down. Depending on the pump and
Current Display Window
The 2iB SC10 has a display of the motor current. It is very useful for the operators to see the current display when adjusting the
stop current. So including a window in the switchboard door helps.
If you don't want the operators to adjust the setpoint, use a cover or door.
If you want only maintenance staff and not normal operators to adjust the Stop Current, then either:
Mount the Pushbuttons behind a cover or door like this
o
You could use a transparent plastic cover or a steel/stainless door.
Or, use lockable pushbuttons.
the measured Current.
hydraulics, the setpoint may need adjustment to achieve optimal detection of snoring.
3