Emerson FB1100 Replacement Manual - Page 6

Browse online or download pdf Replacement Manual for Accessories Emerson FB1100. Emerson FB1100 8 pages. Flow computer coin cell battery field
Also for Emerson FB1100: Termination Board Field Replacement Manual (18 pages), Replacement Manual (18 pages), Field Replacement Manual (14 pages), Field Replacement Manual (20 pages), Field Replacement Manual (8 pages), Field Replacement Manual (8 pages)

Emerson FB1100 Replacement Manual
FB1100/FB1200 Flow Computer Coin Cell Battery Field Replacement Guide
D301854X012
November 2020
7.
8.
9.
10.
4
Removing/Replacing the Coin Cell Battery
Insert the new coin cell battery in the slot. The positive side (+) must be on top.
CAUTION
When inserting the SRAM coin cell battery push the battery gently into its slot until it
stops. The battery should slide in easily. Do not use excessive force.
To replace the HMI module, line up the printed circuit board (PCB) with the slot on the back
and gently press it back on. Tighten the four captive fastening screws with a torque of 4 to 6
in-lbs (0.5 to 0.7 N-m).
Carefully align the end cap threads with the threads of the enclosure and replace the front
end cap. Screw the end cap clockwise (eight full turns) until it is tightly sealed to the
enclosure. End caps must have at least 8 full threads engaged upon reassembly.
Note
If you need more leverage, place a long screwdriver or other appropriate tool across the two
notches in the end cap to act as a pry bar.
If applicable, tighten the retaining clamp onto the end cap using a 3mm hexagonal wrench.
When tightening, torque to 10 to 12 in-lbs (1.1 to 1.4 N-m).