AGS Merlin 1000S User & Installation Manual - Page 4
Browse online or download pdf User & Installation Manual for Controller AGS Merlin 1000S. AGS Merlin 1000S 10 pages. Gas utility isolation controller
Also for AGS Merlin 1000S: Installation, Operation And Maintenance Manual (10 pages), Installation & Operation Manual (12 pages), Installation & Operation Manual (16 pages)
Merlin 1000S
Gas Utility Controller
(4)
[PRESSURE SENSOR]
Gas Pressure Transducer
The terminals marked pressure sensor "+ - IN ".These wire to the gas pressure transducer
which is screwed into the downstream port on the gas solenoid valve (see wiring below).
ENSURE THE TRANSDUCER IS CONNECTED TO THE DOWNSTREAM PORT.
Operating Pressure = 0.17psi min - 1.45psi max
(5)
[EM REMOTE]
Remote Emergency Shut Off Buttons
These connections are linked out as a factory setting. (fig1)
Remote emergency shut-off buttons should be volt free and
wired to the Merlin panel using a Plenum Security Cable. White,
18/2 (18AWG 2 Conductor), stranded, CMP or similar.
(6)
[GAS DETECTOR]
Gas Detectors
These terminals are [+ -] and [
These can be wired to various Merlin gas detectors.
For multiple detector wiring consult the gas detector manual (see example wiring below).
If no detector is being used leave the link in [
Rev: 04 Date: 15-08-18
] and should be volt free dry contact connections.
] (fig2)
User & Installation Manual
fig1
fig2
4