AGS Parksafe Control Panel Installation & Operation Manual
Installation & Operation Manual
Silence & Reset
To silence the internal buzzer – press the Silence button on the front panel.
This will also silence any external audio sounders connected to the panel.
If the system reaches alarm condition – the panel will need to be reset when the gas
levels detected return to a safe level.
Check the detector status pages to identify where gas has been detected and if levels
have returned to a safe condition before resetting the system.

Accessing Detector Status Information

To access detector status information screens –
Press the 'Gas Detection' section on screen any time.
Switch between pages by touching the relevant page button.
Each page can display up to 4 detectors as follows:
a.
ID: The ID configured via switches on each detector board.
b.
Serial Number: The unique serial number for that detector.
c.
Gas: The target gas that the detector is monitoring.
d.
Status: The status of gas levels, errors and messages.
e.
Value: The concentration value of gas detected.
To return to the main screen, press the home button on screen.

Detector Status

GOOD
o
PRE ALARM
o
ALARM
o
FAULT
o
END OF LIFE
o
SERVICE
o
-- X --
o

Gas Alarm Levels

GAS
Carbon Monoxide (CO)
Nitrogen Dioxide (NO
AGS Parksafe Panel - IOM Iss: 6 10-20
Gas levels are safe / No error conditions.
Gas detected has reached pre-alarm levels.
Gas detected has reached alarm levels.
Gas sensor module issue. Contact your supplier.
The gas sensing element has reached the end of its expected lifecycle.
Gas sensing element requires periodic bump test/service.
Detector signal lost, not installed or not configured correctly.
GOOD
> 25 ppm
)
< 0.7 ppm
2
PRE-ALARM
25 -100 ppm
0.7 - 2 ppm
Parksafe
ALARM
> 100 ppm
> 2 ppm