Kohler 14/20RESAL Installation Manual - Page 23

Browse online or download pdf Installation Manual for Portable Generator Kohler 14/20RESAL. Kohler 14/20RESAL 44 pages. Residential/commercial generator sets

Kohler 14/20RESAL Installation Manual
1.8.5

Transfer Switch Connection

Connect the ATS or remote start/stop switch. Connect
the load leads from the generator set to the Emergency
source lugs on the ATS.
communication leads through separate conduit. All
connections must comply with applicable state and local
codes.
Note: Do not use the Kohlerr Model RRT transfer
switch with the 14/20RESA or 14/20RESAL
generator set.
Communication connections for a Kohlerr
Model RXT transfer switch:
See Figure 1-19.
Use Belden #9402 or equivalent
20 AWG shielded, twisted-pair cable to connect P10-1
Generator Set
Generator Set Terminal Block TB1.
See Figure 1-6 for location. Check the
decal on the generator set for terminal block
connections.
Note: Generator set terminal block (TB1) connections 3 and 4 are NOT USED with the Model RXT ATS.
1. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable
Figure 1-19 Model RXT Transfer Switch Communication Connection to Generator Set Terminal Block
TP-6803 12/11
Route low-voltage
Connect one end of each cable shield to
GROUND at the generator set.
GND
A
A
RBUS
B
B
PWR
PWR
12 VDC
COM
COM
4
3
1
TB1
through P10-4 on the transfer switch interface module to
the generator set terminal block TB1 connections A, B,
PWR, and COM.
See Section 1.8.6 for the maximum cable length.
Note: Connections 3 and 4 on the generator set are not
used with the Model RXT transfer switch.
Engine start connection for other transfer
switches or a remote start/stop switch:
Connect the engine start leads from the transfer switch
or remote start switch to terminals 3 and 4 on the
terminal block. See Figure 1-20. Route the engine start
leads through separate conduit from the AC power and
load leads.
A
B
PWR
COM
Leave one end of each cable shield disconnected.
If accessory modules (PIM or LCM) are connected,
see Section 1.8.6.
Interface Board on the
Model RXT Transfer Switch
RXT
Section 1 Installation
23