Generator Set
Generator Set Terminal Block TB1.
See Figure 1-6 for location. Check the
decal on the generator set for terminal block
connections.
1. Engine start leads 3 and 4. See the ATS manual for cable size specifications.
Figure 1-20 Engine Start Connections with Transfer Switch Models RDT or RSB
1.8.6
System Connections with
Accessory Modules
See Figure 1-22 through Figure 1-26 for connection
options with up to three accessory modules. Accessory
modules can include one Model RXT transfer switch,
one programmable interface module (PIM), and/or one
load control module (LCM).
See Figure 1-21 for the maximum total cable length with
1, 2, or 3 accessory modules per cable run.
Cable (TB1- -PWR and COM)
Belden #9402 or equivalent 20AWG
14 AWG
12 AWG
Figure 1-21 Total Cable Lengths with Accessory Modules Connected in Series (daisy-chain)
24
Section 1 Installation
TB1
A
B
PWR
COM
1
4
1
3
D
Use Belden #9402 (4-conductor) or equivalent 20
AWG shielded, twisted-pair cable. Note the shield
connections shown in Figure 1-22.
D
Belden #8723 (2-conductor) shielded twisted-pair
cable can be used for connections A and B, and
#12--14 AWG wire can be used for the COM and PWR
connections. The maximum total cable length is the
value shown for #12 or #14 AWG wire in Figure 1-21.
Maximum length per run, meters (ft.)
Number of Modules (ATS, PIM, and LCM) per Run
1 Module
61
(200)
152
(500)
152
(500)
ATS
Models RDT
or RSB
2 Modules
3 Modules
31
(100)
21
152
(500)
122
152
(500)
152
TP-6803 12/11
tp6809
(67)
(400)