DFE STEADYWEB 6 Quick Start Manual - Page 8

Browse online or download pdf Quick Start Manual for Controller DFE STEADYWEB 6. DFE STEADYWEB 6 12 pages. Tension controller
Also for DFE STEADYWEB 6: Operating Instructions Manual (20 pages)

DFE STEADYWEB 6 Quick Start Manual
Some PID (Proportional, Integral and Derivative) tuning may be
necessary to control tension optimally. Refer to SECTION 6 -
TUNING ADJUSTMENTS of The Manual for a PID control
overview and tuning procedure. Use the PID Tune View display
located at Menu > Calibration Menu > Tune PID Values to adjust
the PID terms for optimal control. See SECTION 5 - USER
INTERFACE OVERVIEW of The Manual for information on how
to utilize the PID Tune View display.
OPERATING INSTRUCTIONS
After calibrating, configuring and tuning the controller, save the
setup at Operator Menu > Store / Delete Setup, by selecting Store
Setup, scrolling to the desired setup location and pressing the
Select button. Follow the on-screen instructions to name the
setup (it helps to be descriptive), press the OK button, and press
the Save button on the next screen.
To recall a setup, visit Operator Menu > Recall Setup, scroll to the
desired setup and press the Recall button, press Recall again on
the next screen, and press OK.
For more information about saving, recalling and deleting setups,
see SECTION 2 - OPERATING INSTRUCTIONS of The Manual.
6