With no other loads on the transducer roll, ZERO the transducers,
hang a calibration weight of known value with an inelastic rope,
strap or cable, and CALIBRATE the transducer signal, exactly as
instructed in SECTION 6 - CALIBRATION of The Manual. The
calibration weight should weigh at least 10% of your maximum
expected web tension.
When the transducer signal is calibrated, press the Display button
to return to the tension display.
If additional calibration is required for inputs of Line Speed, Roll
Speed or Roll Diameter, refer to SECTION 6 - CALIBRATION of
the The Manual.
Program settings are based on the tension zone in which the
controller is being used. For setting up Unwind, Intermediate and
Rewind Zones, refer to SECTION 7 - SETUP of The Manual.