Dell PowerEdge 4400 Rack Installation - Page 22

Browse online or download pdf Rack Installation for Server Dell PowerEdge 4400. Dell PowerEdge 4400 34 pages. Wake-on-lan (wol) support on dell servers
Also for Dell PowerEdge 4400: Installation Manual (42 pages), Installation Manual (20 pages), Installation Manual (28 pages), Rack Installation (37 pages), Update Manual (8 pages), Information Update (8 pages), User Manual (42 pages), Hardware Installation Manual (40 pages), Installation Manual (36 pages), Manual (15 pages)

Dell PowerEdge 4400 Rack Installation
(Rev. 9/8/00) FILE LOCATION: S:\SYSTEMS\MARCONI\Rackingd\7U\05KCEa00\05KCEeb0.fm
8
Rack Installation Guide

Installing the Slide Assemblies in the Rack

You must allow 7 U (12.25 inches) of vertical space for each PowerEdge system you
install in the rack.
The rails of the rack are marked by small indentations in 1-U increments (see
Figure 6).
1 U (1.75 inches)

Figure 6. One Rack Unit

For more information, see the Dell Rack Advisor software available on the Dell World
Wide Web site at http://support.dell.com.
WARNING: If you are installing more than one computer, install the slide
assemblies so that the first computer is installed in the lowest available
position in the rack.
To determine where to install the slide assemblies in the rack, perform the following
steps:
1.
Place the front of the template over the front rack rails (see Figure 7).
The printing on the template identifies the side facing outward as the template
front.
2.
Position the bottom of the template where the system's lower edge will be
located.
DELL CONFIDENTIAL - Preliminary
9/8/00