Dell EMC VxFlex Ready Node R840 Owner's Manual - Page 29
Browse online or download pdf Owner's Manual for Storage Dell EMC VxFlex Ready Node R840. Dell EMC VxFlex Ready Node R840 44 pages.
Table 21 Particulate contamination specifications (continued)
Particulate contamination
Conductive dust
Corrosive dust
The copper coupon corrosion rate is <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985. The silver coupon
corrosion rate is <200 Å/month as defined by AHSRAE TC9.9.
Table 22 Gaseous contamination specifications
Gaseous contamination
Copper Coupon Corrosion
Silver Coupon Corrosion
Note:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Specifications
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
Note:
This condition applies to data center and non-data
center environments.
Air must be free of corrosive dust.
l
Residual dust present in the air must have a deliquescent
l
point less than 60% relative humidity.
Note:
This condition applies to data center and non-data
center environments.
Specifications
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
Technical specifications
R840xd Owner's Guide
29