Dell Networking Z9500 Getting Started Manual - Page 14

Browse online or download pdf Getting Started Manual for Switch Dell Networking Z9500. Dell Networking Z9500 34 pages. Z9500 switch
Also for Dell Networking Z9500: Installation Manual (47 pages)

Dell Networking Z9500 Getting Started Manual

Securing the Chassis Ground

After you mount the chassis, secure the chassis ground as follows:
1.
Locate the chassis ground connector nuts on the chassis rear.
2.
Install the grounding cables to the ground nuts. The grounding cable must comply with your local
electrical codes in size and color (typically the color is green or green with yellow stripe).
NOTE: For proper ventilation, position the chassis in an equipment rack (or cabinet) with a
minimum of 5 inches (12.7 cm) of clearance around exhaust vents. The acceptable ambient
temperature ranges are listed in the Environmental Parameters section.
Use M5 screws.
3.
Tighten the screws (torque should be between 18 and 24 inch/lbs).
4.
Connect the opposite end of the grounding cable to the nearest appropriate facility grounding post.
Figure 3. Cable Connector

Installing Fan Modules

The chassis requires five fan modules to be installed for normal configuration. The airflow direction must
be from I/O to Utility.
Important Points to Remember for Installing a Fan Module
14
Getting Started Guide