Power Supplies

The Z9100–ON ships with two AC or DC power supplies.
The Z9100–ON supports AC or DC power supplies with two air-flow directions (from the I/O to the PSU
and from the PSU to the I/O). Two PSUs are required for full redundancy, but the system can operate with
a single PSU.
The PSUs are field replaceable. When running with full redundancy (two power supplies installed and
running), you can remove and replace one PSU without disrupting traffic.
CAUTION: To prevent electrical shock, ensure that the Z9100-ON is grounded properly. If you do
not ground your equipment correctly, excessive emissions may result. Use a qualified electrician
to ensure that the power cables meet your local electrical requirements.
NOTE: If you use a single PSU, install a blank plate in the other PSU slot. Dell Networking
recommends using power supply 2 (PSU2) as the blank plate slot. Use a #1 Philips screw driver to
install the blank plate.
NOTE: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist
or heel ground strap when handling the Z9100–ON and its components.

Components

The following power supply options are available for the Z9100–ON.
AC or DC power supply with integrated fan
AC or DC power supply with integrated reverse flow fan
Power supply 1 (PSU1) is on the left side of the chassis; power supply 2 (PSU2) is on the right side of the
chassis.
Figure 11. Z9100–ON Power Supply Units (PSUs)
24
5
Power Supplies