Miller XMT 304 Owner's Manual - Page 19

Browse online or download pdf Owner's Manual for Welding System Miller XMT 304. Miller XMT 304 40 pages. 4-rack and 6-rack
Also for Miller XMT 304: Owner's Manual (26 pages), Owner's Manual (37 pages)

Miller XMT 304 Owner's Manual

5-2. Selecting Cable Sizes*

NOTICE − The Total Cable Length in Weld Circuit (see table below) is the combined length of both weld cables. For example, if the power source
is 100 ft (30 m) from the workpiece, the total cable length in the weld circuit is 200 ft (2 cables x 100 ft). Use the 200 ft (60 m) column to determine
cable size.
100 ft (30 m) or Less
10 − 60%
Duty
Welding
Cycle
Amperes
2
AWG (mm
)
100
4 (20)
150
3 (30)
200
3 (30)
250
2 (35)
300
1 (50)
350
1/0 (60)
400
1/0 (60)
500
2/0 (70)
600
3/0 (95)
This chart is a general guideline and may not suit all applications. If cable overheats, use next size larger cable.
*
**Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.
2
( ) = mm
for metric use.
***For distances longer than those shown in this guide, see AWS Fact Sheet No. 39, Welding Cables, available from the American Welding
Society at http://www.aws.org.

5-3. Weld Output Terminals

1
Weld Cable Size** and Total Cable (Copper) Length in Weld Circuit
150 ft
(45 m)
60 − 100%
Duty Cycle
2
AWG (mm
)
4 (20)
4 (20)
3 (30)
2 (35)
2 (35)
1 (50)
1 (50)
1/0 (60)
1/0 (60)
2/0 (70)
2/0 (70)
3/0 (95)
2/0 (70)
3/0 (95)
3/0 (95)
4/0 (120)
4/0 (120)
2x2/0 (2x70)
2
Not Exceeding***
200 ft
250 ft
(60 m)
(70 m)
10 − 100% Duty Cycle
AWG (mm
3 (30)
2 (35)
1 (50)
1/0 (60)
1/0 (60)
2/0 (70)
2/0 (70)
3/0 (95)
3/0 (95)
4/0 (120)
4/0 (120)
2x2/0 (2x70)
4/0 (120)
2x2/0 (2x70)
2x2/0 (2x70)
2x3/0 (2x95)
2x3/0 (2x95)
2x4/0 (2x120)
300 ft
350 ft
(90 m)
(105 m)
2
)
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
3/0 (95)
4/0 (120)
4/0 (120)
2x2/0 (2x70)
2x2/0 (2x70)
2x3/0 (2x95)
2x3/0 (2x95)
2x3/0 (2x95)
2x3/0 (2x95)
2x4/0 (2x120) 2x4/0 (2x120)
2x4/0 (2x120)
3x3/0 (3x95)
3x3/0 (3x95)
3x4/0 (3x120) 3x4/0 (3x120)
Ref. S-0007-M 2017−08
!
Turn off power before connecting
to weld output terminals.
!
Do not use worn, damaged, un-
dersized, or repaired cables.
1
Positive (+) Weld Output Terminal
2
Negative (−) Weld Output Terminal
Ref. 801 192-A / output term1 2015−02
OM-2208 Page 15
400 ft
(120 m)
1/0 (60)
3/0 (95)
4/0 (120)
2x2/0 (2x70)
2x3/0 (2x95)
2x4/0 (2x120)
3x3/0 (3x95)