ABB ISL-A 24 Instruction Manual - Page 4
Browse online or download pdf Instruction Manual for Controller ABB ISL-A 24. ABB ISL-A 24 4 pages. Device for insulation permanent control for isolated networks it
DIMENSIONS
—
TECHNICAL FEATURES
Auxiliary voltage supply
Maximum consumption
Measure current
Internal impedance
Threshold tripping
Tripping delay
Signalling and button
Output
Working and storing temperature
Relative humidity
Insulation test
Mounting position
Wiring type
Protection degree
Mounting according DIN 50022
Weight
Standards
For application not described in this manual it's better to see specific document or to contact the technical
service.
—
NOTE
At reason of the evolution of standards and products, the company reserves to modify in every time the features of the product described
in this document, that it's necessary to verify preventively.
The liability of the producer for damage caused by defect of the product "can be reduced or deleted (...) when the damage is caused joint
by a defect of product or for blame of the damaged or a person of which the damaged is responsible" (Article 8, 85/374/CEE).
1
2024-01-24
24-48V 50-60Hz/d.c. ± 20%
3 VA-3W
max 0,5 mA
50 kΩ
Settable 10 ÷ 60 kΩ (5 levels with micro-switches)
About 0.2 seconds
led ON, led TRIP, led +, led -
Relay changeover contact NO-C-NC max 250V 5A
-10 ÷ 60°C / -20 ÷ 70°C
≤ 95 %
2,5 kV 60 sec. / 4 kV imp. 1,2/50μs
Any
Screw terminals / cross section cables 4 mm²
Front with cover: IP 40 – Enclosure: IP 20
Snap on DIN rail 35mm / 3 modules 17,5 mm
About 300 g
Safety EN 61010-1
Electromagnetic compatibility IEC-EN 61326-1
Snap on DIN rail 35mm
(DIN 50022)
3 modules 17,5 mm
4/4