Also for Siemens SIMATIC ET 200S: Operator's Manual (18 pages), Manual (16 pages), User Manual (16 pages), Manual (37 pages), Manual (24 pages), Function Manual (40 pages), Operating Instructions (4 pages), Original Operating Instructions (19 pages), Original Operating Instructions (20 pages), Manual (34 pages), Manual (14 pages), Manual (24 pages), Original Operating Instructions (17 pages), Original Operating Instructions (19 pages), Manual (16 pages), Manual (28 pages), Manual (12 pages), Manual (32 pages), Manual (18 pages), Manual (12 pages), Manual (28 pages), Manual (22 pages), Manual (22 pages), Manual (36 pages), Manual (16 pages)

Siemens SIMATIC ET 200S User Manual

Properties

1.1

2AI U HF analog electronic module (6ES7134-4LB02-0AB0)

Properties
● 2 inputs for measuring voltage
● Input ranges:
● Isolated from the load voltage L+
● Permitted common-mode voltage between the channels 100 VAC
● Supports isochronous operation
● Supports I&M functions
General terminal assignment
Note
Terminals 4, 8, A4, A8, A3 and A7 are only available at specified terminal modules.
Terminal
Assignment Terminal
1
M
0+
2
M
0-
3
n.c.
4
n.c.
A4
AUX1
A3
AUX1
2AI U HF analog electronic module (6ES7134-4LB02-0AB0)
Manual, 04/2007, A5E01076007-01
– ± 5 V, resolution 15 bits + sign
– ± 10 V, resolution 15 bits + sign
– 1 V to 5 V, resolution 15 bits
– Minimum time for the isochronous DP cycle (T
– Minimum conversion time of the input modules (T
Terminal assignment for 2AI U HF (6ES7134-4LB02-0AB0)
Assignment
5
M
1+
6
M
1-
7
n.c.
8
n.c.
A8
AUX1
A7
AUX1
M
: Input signal "+", channel n
n+
M
: Input signal "-", channel n
n-
n.c.: Not connected (max. 30 V DC can be connected)
AUX1: Protective-conductor terminal or potential bus (freely usable
up to 230 VAC)
): 0.7 ms
DPmin
): 0.5 ms
WEmin
Notes
1