Also for Siemens SIMATIC ET 200SP: Manual (40 pages), User Manual (21 pages), Manual (34 pages), Manual (48 pages), Manual (30 pages), Manual (34 pages), Product Information (38 pages), Manual (37 pages), Manual (36 pages), Manual (44 pages), Manual (31 pages), Manual (35 pages), Manual (23 pages), Manual (34 pages), Manual (29 pages), Manual (33 pages), Manual (31 pages), User Manual (32 pages), Manual (31 pages), Manual (28 pages), Manual (41 pages), Manual (32 pages), Manual (49 pages), Manual (24 pages), Manual (34 pages), Manual (41 pages), Manual (30 pages), Manual (31 pages), Manual (27 pages), Manual (24 pages), Manual (24 pages), Manual (25 pages), Manual (49 pages), Manual (40 pages), Manual (38 pages), Manual (39 pages), Product Information (24 pages), Manual (32 pages), Product Information (10 pages), Equipment Manual (43 pages), Manual (33 pages), Equipment Manual (44 pages), Original Operating Instructions (6 pages), Manual (35 pages), Manual (28 pages), Equipment Manual (32 pages), Manual (50 pages), Manual (30 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), Manual (44 pages), Manual (33 pages), Equipment Manual (42 pages), Original Instructions Manual (16 pages)

Siemens SIMATIC ET 200SP Configuration Manual
3 Configuration
3.2.3

Adjusting the real time settings

To make sure that all IO controllers and "Shared Devices" are operated with the
appropriate send clock and the update times are correctly calculated due to the
communications burden, you need to adjust and check the following settings.
Proceed as follows:
1. In project 1 / project 2, mark the interface module of the "Shared Device" in the
network view.
2. In the inspector window, navigate to:
"PROFINET interface" > "Advanced options" > "Real time settings" > "IO cycle".
In the "Shared Device" area, set the number of project-external IO controllers.
Figure 3-7
Note
The maximum possible number of IO controllers depends on the IO device and
is store in the GSD file.
SharedDeviceKonfig
Entry ID: 109741600,
V1.0,
11/2016
15